Model Number | Voltage | 5hr Rate |
20hr Rate |
100hr Rate |
Watts Per Cell |
Weight (lb.) | Length (in.) | Width (in.) | Height* (in.) |
ES17-12 | 12 | 15.3 | 18 | N/A | N/A | 13.82 | 7.13 | 2.99 | 6.57 |
Nominal
Voltage (V): |
12V |
||
Nominal Capacity: | 20hour rate ( 0.9A
to 10.50V ) 18Ah |
||
10hour rate ( 1.8A
to 10.50V ) 18Ah |
|||
5hour rate ( 3.06A
to 10.20V ) 15.3Ah |
|||
1C ( 18A to 9.60V
) 8.1Ah |
|||
3C ( 54A to 9.60V
) 6.48Ah |
|||
Weight: |
13.82 Lbs. (6.283
kg) |
||
Internal
Resistance (at 1KHz): |
10 mΩ |
||
Maximum Discharge Current for 30 seconds: | 360A |
||
Maximum Discharge Current for 5 seconds: | 720A | ||
Operating Temperature Range: | Charge 0°C(32°F)
to 40°C (104°F) |
||
-15°C(5°F) to 50°C
(122°F) |
|||
-15°C(5°F) to 40°C
(104°F) |
|||
Charge Retention (shelf life) at 20°C (68°F): | 1 month 92% |
||
3 month 90% |
|||
6 month 80% |
|||
Charging Methods at 25°C (77°F) Cycle use: | Charging
Voltage 14.4 to 15.0V |
||
Maximum Charging
Current 5.4A |
|||
Standby use:
|
Float Charging Voltage
13.50 to 13.80V |
||
Life expectancy Cycle Use: | 100% depth of
discharge 250 cycles |
||
80% depth of
discharge 350 cycles |
|||
50% depth of
discharge 550 cycles |
|||
Standby Use:
|
3~5 years |
||
Case Material:
|
ABS |
||
(94-HB & 94V-0
flame retardant case) |
|||
Terminal:
|
F3 |
||
|